Skip to content
BestCalculators
Free online calculators and converters

Electrical & Tech

Voltage Drop Calculator: Wire Size and Run Length

Work out voltage drop over a wire run, check it against the 3% guideline, and find the longest run that gauge can carry.

Copper carries better; aluminium is cheaper and lighter. The constant is ohms per circular-mil-foot.

American Wire Gauge. The numbers run backwards — smaller gauge means thicker wire and less drop.

Single phase counts the wire out and back, so the length doubles. Three phase uses √3 instead.

V
A

The actual load, not the breaker size — though sizing to the breaker is the cautious choice.

ft

Panel to load, measured one way. The formula doubles it for you — do not double it yourself.

Voltage drop

6.58%

7.9 V lost, leaving 112.1 V at the load. The guideline is 3% on a branch circuit, and this run may be up to 46 ft to stay under it.

Voltage lost in the wire
7.9V

Turned into heat along the run. It is not stolen from the meter — you pay for it either way.

Voltage reaching the load
112.1V

Motors are the unforgiving case: undervoltage makes them draw more current, which drops the voltage further and cooks the windings.

Inside the 3% guideline
0

1 yes, 0 no. It is a recommendation in an informational note rather than a hard rule — but inspectors and equipment both expect it.

Longest run at 3%
46ft

With this gauge, material and load. Past it you go up a size, raise the voltage, or accept the drop deliberately.

Longest run at 5%
76ft

Five percent is the total allowance for feeder and branch combined, so spending it all here leaves nothing for the rest.

Power burned in the wire
158W

Drop times current. On a long run this is a permanent space heater buried in a wall.

That loss at 8 hours a day, $0.15 a kWh
$69.22

A rough figure to weigh against the price of thicker wire, which is paid once.

Drop if the supply were doubled
1.646%

A quarter of the drop, because doubling voltage halves current and halves the percentage again. This is why long runs go to 240 V.

Resistance of the run
0.3951Ω

Both conductors together. Multiply by the current and you have the drop above — it is only Ohm’s law with a long wire.

Run length in metres
30.5m

How to use this calculator

  1. Select your Conductor material as either Copper or Aluminium from the dropdown menu.
  2. Choose your Wire size using the American Wire Gauge options from 14 AWG up to 4/0 AWG.
  3. Pick your Circuit configuration as either Single phase or Three phase depending on your installation.
  4. Enter your Supply voltage, the actual Current the load draws in amperes, and your One-way run length in feet.

Understanding Voltage Drop and Why It Happens

Every foot of wire acts as a tiny resistor. When electricity flows through a conductor, energy is lost as heat due to the inherent resistance of the metal. This means the voltage drop calculator output is not just a theoretical number; it represents real electrical pressure lost along the line. If you start with 120 volts at the panel, a long run or an undersized cable might deliver only 112 volts to your appliance. That missing energy vanishes into the walls as warmth, wasting electricity and forcing motors or heating elements to work harder.

The nec 3 percent voltage drop guideline exists to protect equipment from overheating and failing prematurely. While the National Electrical Code often lists this percentage as a recommendation for branch circuits rather than a strict mandate, ignoring it invites trouble. Motors will draw more current to compensate for lower voltage, causing them to run hot and burn out their windings prematurely. Lighting will dim, and sensitive electronics may reset or refuse to operate correctly under low-voltage conditions.

The Hidden Math Behind the Cable Run

When you enter your parameters, the engine behind this wire size calculator performs a specific sequence of arithmetic without asking you to do the heavy lifting. The formula relies on a constant known as K, which represents the direct-current resistance of a mil-foot of wire. For copper vs aluminum wire comparisons, K is set at 12.9 for copper and 21.2 for aluminium. Aluminium has higher electrical resistance, which is why it requires a larger gauge to carry the same current safely over distance.

The silent adjustment happening in the background involves your cable run length calculator inputs. For single-phase circuits, the tool automatically multiplies your one-way distance by two. This accounts for the complete electrical loop: current must travel out to the load on the hot wire and return to the source on the neutral wire. For three-phase circuits, the multiplier changes to the square root of three, reflecting the phase-to-phase balancing inherent in three-phase electrical theory. You enter only the one-way distance from the panel to the load, and the logic handles the doubling for you.

Choosing the Right Gauge and Material

American Wire Gauge numbers run backward from what most people expect. A smaller awg voltage drop number means a thicker physical wire with more cross-sectional area measured in circular mils. For instance, 14 AWG has only 4,110 circular mils and creates significant resistance over distance, whereas 4/0 AWG boasts 211,600 circular mils and can carry massive loads over long spans with minimal loss. When selecting your conductor, remember that copper carries current better and resists oxidation more reliably, while aluminium offers a cheaper and lighter alternative for large feeder runs.

AWG SizeCircular MilsCopper Max Run at 120V/15AAluminium Max Run at 120V/15A
14 AWG4,110 cmil52 ft31 ft
12 AWG6,530 cmil83 ft50 ft
10 AWG10,380 cmil132 ft80 ft
8 AWG16,510 cmil210 ft128 ft
6 AWG26,240 cmil334 ft203 ft

Costs, Limitations, and When to Call an Expert

Energy lost in a cable is not just an efficiency problem; it costs real money. The calculation for power burned in the wire converts that resistance into watts and estimates your annual waste based on continuous usage at typical electricity rates. Over a year, an undersized wire feeding a constant garage heater or workshop tool can waste dozens of dollars in electricity that simply heats up the inside of your conduit.

Despite its precision, this tool relies on ideal conditions and basic resistivity constants at standard operating temperatures. It does not account for high ambient temperatures in attics, grouped conductors inside tightly packed conduits, or harmonic distortion from modern electronic loads, all of which increase effective wire resistance. For complex industrial installations, multi-branch runs, or any high-voltage commercial project where safety violations carry severe liabilities, always consult a licensed electrician or structural electrical engineer to verify your final design.

The formula

single phase: VD = 2 × K × I × L ÷ CMthree phase: VD = √3 × K × I × L ÷ CMK = 12.9 copper, 21.2 aluminium · L = one-way feet · CM = circular milsmax length at 3% = 0.03 × V × CM ÷ (2 × K × I)

Frequently asked questions

What is considered an acceptable voltage drop?

The standard industry guideline recommends keeping total voltage drop under 3 percent for branch circuits and feeder lines combined. A maximum of 5 percent total drop from the service entrance to the furthest load is generally the outer limit for safe and efficient operation. Exceeding these thresholds causes motors to overheat and reduces the lifespan of connected electrical equipment.

Why does the calculation double the wire length?

Electrical current requires a complete circuit to flow, meaning it travels out from the power source on the hot conductor and returns on the neutral or another hot conductor. Because the electricity must make a round trip, the resistance of both the outgoing and returning wire contributes to the total loss. The tool automatically accounts for this complete loop by multiplying your one-way measurement by two for single-phase systems.

Should I use copper or aluminium wire for my project?

Copper offers superior conductivity and durability, making it the standard choice for residential branch circuits and smaller installations. Aluminium is significantly lighter and less expensive, which makes it popular for large service entrance cables and long feeder runs where thicker gauges are required. When using aluminium, you must use larger wire sizes and specialized anti-oxidation paste at all termination points to prevent loose connections.

What happens if my wire size is too small for the run?

An undersized wire introduces high electrical resistance that converts a portion of your electricity into unwanted heat instead of delivering it to your appliance. This results in dimming lights, sluggish motor performance, and potential fire hazards due to overheating insulation inside the walls or conduit. Furthermore, appliances drawing power through low voltage will pull higher amperage to compensate, accelerating wear and tear on internal components.

Does the actual current draw differ from the breaker size?

Yes, the actual current draw is the continuous amperage your appliance or equipment pulls during normal operation, which is often lower than the rating of the protective circuit breaker. While sizing your wire based on the actual load is standard practice for voltage drop, sizing the wire to match the breaker rating is the safer choice if the connected load might change in the future.

Sources

Last reviewed . Results are for general guidance and are not professional advice.